BJZPR - LEAD-ACID BATTERY
- MSDS: BJZPR
- Manufacturer: EXIDE CORP
- Product Name: LEAD-ACID BATTERY
- National Stock Number: 6140-00-822-0414
Product Identification
Product ID:LEAD-ACID BATTERY
MSDS Date:05/01/1991
FSC:6140
NIIN:00-822-0414
MSDS Number: BJZPR
Responsible Party
READING, PA 19601
US
Emergency Phone: 215-378-0757
Info Phone: 215-378-0757
Cage: 60038
Contractor
Telephone: 330-471-6587/330-471-6470 FAX
Cage: 60038
Ingredients
LEAD (SARA III)
CAS: 7439-92-1
RTECS: OF7525000
Fraction By Weight: 60%
OSHA PEL 0.05 MG/M3;1910.1025
ACGIH TLV: 0.15 MG/M3;DUST 9192
EPA Report Quantity: 1 LB
DOT Report Quantity: 1 LB
ANTIMONY (SARA III)
CAS: 7440-36-0
RTECS: CC4025000
Fraction By Weight: 2%
OSHA PEL 0.5 MG/M3
ACGIH TLV: 0.5 MG SB/M3; 9192
EPA Report Quantity: 5000 LBS
DOT Report Quantity: 5000 LBS
ARSENIC (SARA III)
CAS: 7440-38-2
RTECS: CG0525000
Fraction By Weight: 0.2%
OSHA PEL 0.5 MG/M3 (AS)
ACGIH TLV: 0.01,A1 MG/M3; 9394
EPA Report Quantity: 1 LB
DOT Report Quantity: 1 LB
CALCIUM, METAL
CAS: 7440-70-2
RTECS: EV8040000
Fraction By Weight: 0.2%
TIN
CAS: 7440-31-5
RTECS: XP7320000
Fraction By Weight: 0.2%
OSHA PEL 2 MG/M3
ACGIH TLV: 2 MG/M3; 9192
SULFURIC ACID (SARA III)
CAS: 7664-93-9
RTECS: WS5600000
Fraction By Weight: 10-30%
OSHA PEL 1 MG/M3
ACGIH TLV: 1 MG/M3; 9192
EPA Report Quantity: 1000 LBS
DOT Report Quantity: 1000 LBS
CASE MATERIAL, (MADE OF POLYPROYLENE, POLYSTYRENE, STYRENE
Fraction By Weight: 5-10%
Hazards
LD50 LC50 Mixture:NOT SPECIFIED BY MANUFACTURER.
Routes of Entry: Inhalation:YES Skin:YES Ingestion:YES
Reports of Carcinogenicity:NTP:YES IARC:YES OSHA:YES
Health Hazards Acute and Chronic:LEAD EXPOSURE MAY CAUSE STOMACH
CRAMPS, ANEMIA, NERVE DAMAGE. SULFURIC ACID MAY CAUSE EROSION OF
THE TEETH.
Explanation of Carcinogenicity:ARSENIC IS CONSIDERED CARCINOGENIC BY
NTP, IARC OR OSHA.
Effects of Overexposure:COUGHING FROM ACID MIST.
Medical Cond Aggravated by Exposure:NONE SPECIFIED BY MANUFACTURER.
First Aid
First Aid:REMOVE FROM EXPOSURE. FLUSH ELECTROLYTE FROM SKIN WITH WATER.
FLUSH EYES FOR 15 MINUTES WITH WATER. SEE PHYSICIAN.
Fire Fighting
Lower Limits:4.1 % (H2)
Upper Limits:74.2 % (H2)
Extinguishing Media:CARBON DIOXIDE, FAOM, HALOGEN, DRY CHEMICAL
Fire Fighting Procedures:IF BATTERIES ARE ON CHARGE, SHUT OFF POWER.
WATER APPLIED TO ELECTROLLYTE GENERATES HEAT AND CAUSES IT TO
SPATTER.
Unusual Fire/Explosion Hazard:HIGHLY FLAMMABLE HYDROGEN GAS IS
GENERATED DURING CHARGING AND OPERATION OF BATTERIES. TO AVOID RISK
OF FIRE OR EXPLOSION, KEEP SPARKS/IGNITION SOURCES AWAY.
Accidental Release
Spill Release Procedures:DILUTE ACID WITH WATER, NEUTRALIZE WITH
CARBONATE.
Neutralizing Agent:CARBONATE
Handling
Handling and Storage Precautions:KEEP AWAY FROM IGNITION SOURCES DURING
AND AFTER CHARGING.
Other Precautions:DO NOT SHORT TERMINALS WITH TOOLS, ETC.
Exposure Controls
Respiratory Protection:FOR SULFURIC ACID MIST EXPOSURE USE NIOSH/MSHA
APPROVED 1/2 MASK NEGATIVE PRESSURE WITH DUST AND MIST FILTER.
Ventilation:3 - 4 AIR CHANGES PER HOUR.
Protective Gloves:RUBBER OR PLASTIC
Eye Protection:CHEMICAL GOGGLES
Other Protective Equipment:EYEWASH STATION
Work Hygienic Practices:WASH WITH SOAP AND WATER AFTER HANDLING PRODUCT
AND BEFORE EATING, DRINKING OR SMOKING.
Supplemental Safety and Health
NONE SPECIFIED BY MANUFACTURER.
Chemical Properties
HCC:N1
Boiling Pt:B.P. Text:203F,95C
Vapor Pres:10
Vapor Density:>1
Spec Gravity:1.23-1.35
Evaporation Rate & Reference:<1 (BUTYL ACETATE=1)
Solubility in Water:100%
Appearance and Odor:MANUFACTURED ARTICLE; NO APPARENT ODOR. ELECTROLYTE
IS CLEAR LIQUID W/ PEN. ODO
Stability
Stability Indicator/Materials to Avoid:YES
CONTACT OF SULFURIC ACID WITH COMBUSTIBLES AND ORGANIC MATERIALS MA
CAUSE FIRE AND EXPLOSION. REDUCING AGENTS, METALS.
Stability Condition to Avoid:PROLONGED OVERCHARGE; SOURCES OF IGNITION.
Hazardous Decomposition Products:MAY GENERATE ARSINE, STIBINE AND/OR
SULFURIC ACID MIST ON OVERCHARGE.
Disposal
Waste Disposal Methods:RETURN SPENT BATTERY TO SECONDARY LEAD SMELTER.
DISPOSE OF IN ACCORDANCE WITH ALL LOCAL, STATE AND FEDERAL
REGULATIONS.
Disclaimer (provided with this information by the compiling agencies):
This information is formulated for use by elements of the Department
of Defense. The United States of America in no manner whatsoever,
expressly or implied, warrants this information to be accurate and
disclaims all liability for its use. Any person utilizing this
document should seek competent professional advice to verify and
assume responsibility for the suitability of this information to their
particular situation.